TOSHIBA ULTRAKOMPAKTA FREKVENSOMRIKTARE, VF-NC1VEKTOROMRIKTARE 0,1-2,2 kWKompakt
och kraftfull och enkel att använda |
| Standard specifikationer | Allmänna specifikationer | Dimensioner | Katalog | Kabel-dimensionering | Optioner |
- Allmänna specifikationer -
| Item | Specification | |
| Principal control functions |
Control system | Sinusoidal PWM control |
| Related output voltage | Adjustable of output voltage in base freguency setting by the correcting supply voltage (200V) (Unadjustable to any voltage higher than the input voltage). | |
| Output frequency range | 0.5 to 200Hz, default setting: 0.5 to 80Hz, maximum frequency: 30 to 200Hz. | |
| Minimum setting steps of frequency | 0.1Hz: operation panel setting, 0.2Hz: analog input (when the max. frequency is 100Hz). | |
| Frequency accuracy | Digital setting: within +/-0.5% of the
max. frequency (-10 to +50 degreeC) Analog setting: within +/-1.0% of the max. frequency (25 degreeC +/- 10 degreeC) |
|
| Voltage/frequency characteristics | V/f, sensorless vector control, base frequency, base frequency voltage and torque boost amount adjustable | |
| Frequency setting signal | Volume on the front panel, external frequency volume (connectable to a volume with a rated impedance of 3-10kohm), VI terminal (input impedance: 42kohm(voltage: 0-10Vdc) or 250ohm (current: 4-20mAdc)). The characteristic can be set arbitrarily by two-point setting. | |
| Operation specifications |
Start-up frequency/frequency jump | Adjustable within a range of 0.5 to 10Hz/Up to 1 frequency can be adjusted together with their widths. |
| PWM carrier frequency | Selectable from among 2, 4, 8, 12 and 16kHz (Standard default setting: 12kHz) | |
| Acceleration/deceleration time | 0.1 to 3000 seconds, switchable between acceleration/deceleration time 1 and 2. | |
| Retry operation | Number of times of retry selectable (Max.
10 times). If the protection function is activated, the retry function restarts on completion of a check of the main circuit. |
|
| Electric control | Charging of capacitor (Deceleration time can be shortened by activating Forced Shortened Deceleration mode.) | |
| DC braking | Braking start-up frequency: 0 to maximum frequency, braking rate: 0 to 100%, braking time: 0 to 20 seconds. | |
| Input terminal functions (selectable) |
Forward/reverse run input signal, jog run input signal, standby signal, preset-speed operation input signal, reset input signal, etc./Switching between sink/source. | |
| Output terminal functions (selectable) |
Frequency lower limit output signal, frequency upper limit output signal, low-speed detection output signal, specified speed attainment output signal, etc. Open collector, RY output. | |
| Failure detection signal | 1c-contact output: 250Vac/2A, cos = 0.4 | |
| Output for frequency meter output for ammeter |
PWM output: (1mAdc full-scale DC ammeter or 7.5Vdc full-scale DC ammeter/Rectifier-type AC voltmeter, 225% current Max. 1mAdc, 7.5Vdc full-scale) | |
| Protective function |
Protective function | Stall prevention, current limitation, over-current, output short circuit, over-voltage, over-voltage limitation, undervoltage, ground fault, power supply phase failure, output phase failure overload protection by electronic thermal function, armature over-load at start-up, load-side over-torque at start, overheating prevention, detection of analog signal break. |
| Protection against momentary power failure |
Auto-restart/non-stop control after momentary power failure. | |
| Electronic thermal characteristics | Switching between standard motor/constant-torque VF motor, overload trip, overload stall selection. | |
| Display function |
4-digit 7-segments LED | Frequency: inverter output frequency. Alarm: stall alarm "C", overvoltage alarm "P", overload alarm "L", overheat alarm "H". Status: inverter status (frequency, cause of activation of protective function, input/output voltage, output current, etc.) and parameter settings. Free-unit display: arbitrary unit (e.g. rotating speed) corresponding to output frequency. |
| Indicator | Lamps indicating the inverter status by lighting, such as RUN lamp and PRG lamp. | |
| Environments | Use environments | Indoor, altitude: 1000m (Max.), not exposed to direct sunlight, corrosive gas, explosive gas or vibration (less than 5.9m/s2) (10 to 55Hz). |
| Ambient temperature | -10 to 50 degreeC Note)1.2 | |
| Storage temperature | -20 to +65 degreeC | |
| Relative humidity | 20 to 93% (free from condensation and vapor). | |
| Note) 1. Above 40 degreeC: Remove the protective
seal from the top of VF-nC1. Note) 2. Side-by-side installation : 40 degreeC or less (Remove the protective seal from the top of VF-nC1). |